POÊLE THERMOROSSI : TOUS SAVOIR
POÊLE THERMOROSSI : PANNES
ALAC : LA PHASE DE DEMARRAGE DURE 20MIN. A LA FIN DE LA PHASE DE DEMARAGE, L’APPAREIL VERIFIE LA REUSSITE DE L’ALLUMAGE EN CONSULTANT LA SONDE DE TEMPERATURE DES FUMEES. SI LA SONDE DETECTE UNE TEMPERATURE SUPERIEURE A 60°C, L’APPAREIL EST CHAUD, LE DEMARRAGE EST DONC REUSSI ET L’AFFICHAGE PASSE EN « ON ». SI LA SONDE NE DETECTE PAS UNE TEMPERATURE SUPERIEURE A 60°C, L’APPAREIL N’EST PAS CHAUD. L’APPAREIL RALLONGE L’ALLUMAGE DE 5MIN. AU BOUT DES 5MIN SUPPLEMENTAIRES, SI LA SONDE NE DETECTE PAS UNE TEMPERATURE SUPERIEURE A 60°C, L’ALLUMAGE A RATE, L’AFFICHAGE PASSE A « ALAC » ET L’ALIMENTATION EN PELLET EST ARRETEE.
- CAUSES PROBABLES : RESISTANCE ENCRASSEE, RESISTANCE ENDOMMAGEE/USEE, BRULEUR ENCRASSE, SONDE ENCRASSEE, PELLET DE MAUVAISE QUALITE
ALPE : EN PHASE DE FONCTIONNEMENT NORMAL, L’APPAREIL VERIFIE SON BON FONCTIONNEMENT EN CONSULTANT LA SONDE DE TEMPERATURE DES FUMEES. SI LA SONDE DETECTE UNE TEMPERATURE SUPERIEURE A 55°C, L’APPAREIL EST CHAUD, LE FONCTIONNEMENT EST NORMAL ET L’AFFICHAGE RESTE EN « ON ». SI LA SONDE DETECTE UNE TEMPERATURE INFERIEURE A 55°C ET QUE CETTE SITUATION PERDURE PLUS DE 5MIN, L’APPAREIL S’EST REFROIDI. L’AFFICHAGE PASSE A « ALPE » ET L’ALIMENTATION EN PELLET EST ARRETEE.
- CAUSES PROBABLES : RESERVOIR VIDE, BRULEUR ENCRASSE, PELLET DE MAUVAISE QUALITE, SONDE ENCRASSEE.
ALOP : PENDANT TOUTES LES PHASES DE FONCTIONNEMENT, L’APPAREIL VERIFIE SON BON FONCTIONNEMENT EN CONSULTANT LE PRESSOSTAT. SI LA DEPRESSION EST CORRECTE, LE PRESSOSTAT GARDE LE CONTACT FERME, LE FONCTIONNEMENT EST NORMAL ET L’AFFICHAGE RESTE EN « STAR » OU « ON ». SI LA DEPRESSION N’EST PLUS ASSUREE, LE PRESSOSTAT OUVRE LE CONTACT, L’AFFICHAGE PASSE A « ALOP » ET L’ALIMENTATION EN PELLET EST ARRETEE.
- CAUSES PROBABLES : RESERVOIR VIDE, CONDUIT DE FUMEES OBSTRUE, COMPARTIMENT DE FUMEES ENCRASSE, EXTRACTEUR DE FUMEE ENDOMMAGE, CONDUIT FLEXIBLE TRANSPARENT DU PRESSOSTAT ENCRASSE, PRESSOSTAT ENDOMMAGE.
ALTMAX : LE THERMOSTAT A REARMEMENT S’EST DECLENCHE. LE MOTEUR DE VIS (AVEC LE TEMOIN DE FONCTIONNEMENT VERT) N’EST PLUS ALIMENTE.
- CAUSES PROBABLES : SURCHAUFFE IMPORTANTE DU FOYER
AL SMOKE RPM SENSOR : PENDANT TOUTES LES PHASES DE FONCTIONNEMENT, L’APPAREIL VERIFIE SON BON FONCTIONNEMENT EN CONSULTANT LA SONDE HALL. SI LA SONDE HALL DETECTE 0 RPM PENDANT PLUS DE 1MIN, L’AFFICHAGE PASSE A « AL SMOKE RPM SENSOR » ET L’ALIMENTATION EN PELLET EST ARRETEE.
- CAUSES PROBABLES : EXTRACTEUR DE FUMEE DECONNECTE, EXTRACTEUR DE FUMEES ENDOMMAGE, SONDE HALL ENDOMMAGEE.
AL SMOKE FAN : PENDANT TOUTES LES PHASES DE FONCTIONNEMENT, L’APPAREIL VERIFIE SON BON FONCTIONNEMENT EN CONSULTANT LA SONDE HALL. SI LA SONDE HALL DETECTE MOINS DE 800 RPM PENDANT PLUS DE 2MIN, L’AFFICHAGE PASSE A « AL SMOKE FAN » ET L’ALIMENTATION EN PELLET EST ARRETEE.
- CAUSES PROBABLES : EXTRACTEUR DE FUMEE ENDOMMAGE, SONDE HALL ENDOMMAGEE.
AL SMOKE TEMP SENSOR : PENDANT TOUTES LES PHASES DE FONCTIONNEMENT, L’APPAREIL VERIFIE SON BON FONCTIONNEMENT EN CONSULTANT LA SONDE DE TEMPERATURE DES FUMEES.
SI LA SONDE N’EST PLUS DETECTEE PAR LA CARTE ELECTRONIQUE PENDANT PLUS DE 10SEC, L’AFFICHAGE PASSE A « AL SMOKE TEMP SENSOR » ET L’ALIMENTATION EN PELLET EST ARRETEE.
- CAUSES PROBABLES : SONDE DECONNECTEE, SONDE ENDOMMAGEE.
FAILED START
LA PHASE DE DEMARRAGE DURE 20MIN. A LA FIN DE LA PHASE DE DEMARAGE, L’APPAREIL VERIFIE LA REUSSITE DE L’ALLUMAGE EN CONSULTANT LA SONDE DE TEMPERATURE DES FUMEES. SI LA SONDE DETECTE UNE TEMPERATURE SUPERIEURE A LA CONSIGNE, L’APPAREIL EST CHAUD, LE DEMARRAGE EST DONC REUSSI ET L’AFFICHAGE PASSE EN « ON ».
SI LA SONDE NE DETECTE PAS UNE TEMPERATURE SUPERIEURE A LA CONSIGNE, L’APPAREIL N’EST PAS CHAUD. L’APPAREIL RALLONGE L’ALLUMAGE DE 5MIN. AU BOUT DES 5MIN SUPPLEMENTAIRES, SI LA SONDE NE DETECTE PAS UNE TEMPERATURE SUPERIEURE A 60°C, L’ALLUMAGE A RATE, L’AFFICHAGE PASSE A « ALAC » OU « FAILED START » ET L’ALIMENTATION EN PELLET EST ARRETEE.
CAUSES PROBABLES : RESISTANCE ENCRASSEE, RESISTANCE ENDOMMAGEE/USEE, BRULEUR ENCRASSE, SONDE ENCRASSEE, PELLET DE MAUVAISE QUALITE.
NO PELLET
EN PHASE DE FONCTIONNEMENT NORMAL, L’APPAREIL VERIFIE SON BON FONCTIONNEMENT EN CONSULTANT LA SONDE DE TEMPERATURE DES FUMEES. SI LA SONDE DETECTE UNE TEMPERATURE A LA CONSIGNE, L’APPAREIL EST CHAUD, LE FONCTIONNEMENT EST NORMAL ET L’AFFICHAGE RESTE EN « ON ».
SI LA SONDE DETECTE UNE TEMPERATURE INFERIEURE A LA CONSIGNE ET QUE CETTE SITUATION PERDURE PLUS DE 5MIN, L’APPAREIL S’EST REFROIDI. L’AFFICHAGE PASSE A « ALPE » OU « FAILED START » ET L’ALIMENTATION EN PELLET EST ARRETEE.
CAUSES PROBABLES : RESERVOIR VIDE, BRULEUR ENCRASSE, PELLET DE MAUVAISE QUALITE, SONDE ENCRASSEE.
SMOKE NO OUT
PENDANT TOUTES LES PHASES DE FONCTIONNEMENT, L’APPAREIL VERIFIE SON BON FONCTIONNEMENT EN CONSULTANT LE PRESSOSTAT. SI LA DEPRESSION EST CORRECTE, LE PRESSOSTAT GARDE LE CONTACT FERME, LE FONCTIONNEMENT EST NORMAL ET L’AFFICHAGE RESTE EN « START » OU « WORK ».
SI LA DEPRESSION N’EST PLUS ASSUREE, LE PRESSOSTAT OUVRE LE CONTACT, L’AFFICHAGE PASSE A « ALOP » OU « SMOKE NO OUT » ET L’ALIMENTATION EN PELLET EST ARRETEE.
CAUSES PROBABLES : CONDUIT DE FUMEES OBSTRUE, COMPARTIMENT DE FUMEES ENCRASSE, EXTRACTEUR DE FUMEE ENDOMMAGE, CONDUIT FLEXIBLE TRANSPARENT DU PRESSOSTAT ENCRASSE, PRESSOSTAT ENDOMMAGE.
ALTMAX
LE THERMOSTAT A REARMEMENT S’EST DECLENCHE. LE MOTEUR DE VIS (AVEC LE TEMOIN DE FONCTIONNEMENT VERT) N’EST PLUS ALIMENTE.
CAUSES PROBABLES : SURCHAUFFE IMPORTANTE DU FOYER
AL SMOKE RPM SENSOR
PENDANT TOUTES LES PHASES DE FONCTIONNEMENT, L’APPAREIL VERIFIE SON BON FONCTIONNEMENT EN CONSULTANT LA SONDE HALL.
SI LA SONDE HALL DETECTE 0 RPM PENDANT PLUS DE 1MIN, L’AFFICHAGE PASSE A « AL SMOKE RPM SENSOR » ET L’ALIMENTATION EN PELLET EST ARRETEE.
CAUSES PROBABLES : EXTRACTEUR DE FUMEE DECONNECTE, EXTRACTEUR DE FUMEES ENDOMMAGE, SONDE HALL ENDOMMAGEE
AL SMOKE FAN
PENDANT TOUTES LES PHASES DE FONCTIONNEMENT, L’APPAREIL VERIFIE SON BON FONCTIONNEMENT EN CONSULTANT LA SONDE HALL.
SI LA SONDE HALL DETECTE MOINS DE 800 RPM PENDANT PLUS DE 2MIN, L’AFFICHAGE PASSE A « AL SMOKE FAN » ET L’ALIMENTATION EN PELLET EST ARRETEE.
CAUSES PROBABLES : EXTRACTEUR DE FUMEE ENDOMMAGE, SONDE HALL ENDOMMAGEE.
AL SMOKE TEMP SENSOR
PENDANT TOUTES LES PHASES DE FONCTIONNEMENT, L’APPAREIL VERIFIE SON BON FONCTIONNEMENT EN CONSULTANT LA SONDE DE TEMPERATURE DES FUMEES.
SI LA SONDE N’EST PLUS DETECTEE PAR LA CARTE ELECTRONIQUE PENDANT PLUS DE 10SEC, L’AFFICHAGE PASSE A « AL SMOKE TEMP SENSOR » ET L’ALIMENTATION EN PELLET EST ARRETEE.
CAUSES PROBABLES : SONDE DECONNECTEE, SONDE ENDOMMAGEE.